CP-E16-M12-EL (546923) input module
Item number:
OT-FESTO025830
Example illustration
Properties
Per­mis­sion C-​tick,
c UL us - Listed (OL)
KC-​mark KC-​EMV
CE cer­tifi­cate (see de­c­la­ra­tion of con­for­mity) to EU EMC di­rec­tive
Cor­ro­sion re­sis­tant class KBK 1 - low cor­ro­sion stress
LED dis­plays 16 Kanal­sta­tus,
2 Mod­ul­diag­nose,
4 Grup­pen­di­ag­nose
Fuse (short cir­cuit) In­ter­nal elec­tronic fuse Per group
Op­er­at­ing volt­age DC load volt­age [V] 24
Op­er­at­ing volt­age range DC [V] 18 to 30
Input de­bounc­ing time 3 ms (0.5 ms, 10 ms, 20 ms pa­ra­me­ter­is­able)
Max. cu­mu­la­tive cur­rents per mod­ule [A] 0,7
Max. num­ber of in­puts 16
Nom­i­nal op­er­at­ing volt­age DC [V] 24
Po­ten­tial sep­a­ra­tion chan­nel - chan­nel no
Resid­ual rip­ple load volt­age 4 Vss
Switch level Sig­nal 0: <= 6 V,
Sig­nal 1: >= 8.6 V
Bear­ing tem­per­a­ture [°C] -20 to 70
Pro­tec­tion cat­e­gory IP65,
IP67
am­bi­ent tem­per­a­ture [°C] -5 to 50
Char­ac­ter­is­tic curves in­puts IEC1131-​T2
Switch­ing logic in­puts PNP (Pos­i­tive switch­ing)
Fas­ten­ing type With through­way bores,
With Slot rail,
Se­lec­tively:
Ma­te­r­ial in­for­ma­tion RoHs com­pli­ant
Cover ma­te­r­ial PA re­in­forced
Hous­ing ma­te­r­ial PA re­in­forced
Further information:
Weight 290 g / pcs
GTIN 4052568185565
Customs duty number 85389099
Manufacturer Festo
Landefeld Druckluft und Hydraulik GmbH · Konrad-Zuse-Straße 1 · 34123 Kassel · Germany
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
As of: 05.06.2025