CPX-2AE-U-I (526168) analogue module
Item number:
OT-FESTO011211
Example illustration
Properties
Di­men­sions W x L x H 50 mm x 107 mm x 50 mm,
(Incl. link­ing block and con­nec­tors)
Di­ag­no­sis Para­me­tri­er­fehler,
Draht­bruch pro Kanal,
Gren­zw­ertver­let­zung pro Kanal,
Kurz­schluss Ein­gangssig­nal
Pa­ra­me­ter­is­ing Sig­nal­bere­ich pro Kanal,
Daten­for­mat,
Forcen pro Kanal,
Gren­zw­ertüberwachung/Kanal,
Mess­wertglättung,
Überwachung Draht­bruch/Kanal,
Ver­hal­ten nach Kurz­schluss
LED dis­plays 1 Sam­mel­diag­nose
In­ter­nal cycle time 4 ms
Op­er­at­ing volt­age range DC [V] 18 to 30
In­trin­sic power input at op­er­at­ing volt­age Type 50 mA
Nom­i­nal op­er­at­ing volt­age DC [V] 24
Po­ten­tial sep­a­ra­tion chan­nel - in­ter­nal bus Yes, with­out using in­ter­nal sen­sor sup­ply
Po­ten­tial sep­a­ra­tion chan­nel - chan­nel no
Cor­ro­sion re­sis­tant class KBK (In in­te­grated con­di­tion),
1 - low cor­ro­sion stress
Bear­ing tem­per­a­ture [°C] -20 to 70
Pro­tec­tion cat­e­gory De­pends on con­nec­tion block
am­bi­ent tem­per­a­ture [°C] -5 to 50
Max. line length 30 m,
Shielded
Hous­ing ma­te­r­ial PC,
PA re­in­forced
Quan­tity in­puts 2
Fuse (short cir­cuit) In­ter­nal elec­tronic fuse
Weight 0.15 % at 25 °C
Use error lim­its re­lated to am­bi­ent tem­per­a­ture range ±0,5 % für Span­nung­sein­gang
Base error limit at 25 °C ±0,3 % für Span­nung­sein­gang
Data for­mat 12 bit + Sign,
Scal­able to 15 bits
Sen­sor type 0 - 10 V,
0 - 20 mA,
4 - 20 mA
Further information:
Weight 55 g / pcs
GTIN 4052568015626
Customs duty number 85389099
Manufacturer Festo
Landefeld Druckluft und Hydraulik GmbH · Konrad-Zuse-Straße 1 · 34123 Kassel · Germany
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
As of: 05.06.2025