| Design | Angular |
| Based on standard |
EN 60947-5-6, VDI/VDE 3845 |
| Permission |
RCM mark, c UL us (OL) |
| CE certificate (see declaration of conformity) |
to EU EMC directive, to EU EX protection directive (ATEX) |
| Material information |
LABS containing materials included, RoHs compliant |
| Material information | Inductive |
| ambient temperature [°C] | -25 to 100 |
| Control output | NAMUR |
| Switching element function | NC contact |
| Max. switching frequency [Hz] | 3.000 |
| Max. output current DC [mA] | 3 |
| Operating voltage range DC [V] | 8,2 |
| Electrical connection: input |
M12x1, 4 pin, Plug |
| installation position | arbitrary |
| Housing material | PBT |
| Screws material | High-alloyed stainless steels |
| Electrical connection 1, connection pattern | LED yellow |
| Bearing temperature [°C] | -40 to 100 |
| Protection category | IP67 |
| Shock resistance | Shock test with degree of severity 2 to FN 942017-5 and EN 60068-2-27 |
| Oscillation strength | Transport use test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| Degree of contamination | 3 |
| Short circuit resistance | yes |
| Reverse polarity protection | for all electrical connections |
| ATEX gas category | II 1G |
| Ex ignition protection type gas | Ex ia IIC T6...T1 Ga |
| LABS (PWIS) conformity | II 1D |
| Ex ignition protection type dust | Ex ia IIIC T135°C Da |
| Ex protection approval outside of the EU |
EPL Da (IEC-EX), EPL Ga (IEC-EX) |
| Ex ambient temperature |
see ATEX Certificate, see IECEx Certificate |
| Effective inductivity | 100 µH |
| Effective capacity | 100 nF |
| Max. input parameter intrinsically safe circuit |
see ATEX Certificate, see IECEx Certificate |
| Certified awarding point |
IECEx TUN 18.0003X, TÜV 16 ATEX 174269 X |
| Safety Integrity Level (SIL) | SIL 2 |
| {{ $t('shop.all.gewicht') }} | 125 g / pcs |
| {{ $t('shop.all.gtin') }} | 4052568271398 |
| {{ $t('shop.display.artikel.zollwarennummer') }} | 85365019 |
| {{ $t('shop.all.hersteller') }} | Festo |