Dimensions W x L x H |
18.9 mm x 76.6 mm x 124.3 mm
|
Pitch dimension [mm] |
18,9
|
Quantity outputs: |
4
|
Diagnosis via LED |
Error per channel, Error per module
|
Diagnosis via bus |
General errors, Short circuit/overload actuator supply, Short circuit/overload analogue output, Parametering error, Exceeding nominal range, Nominal range not reached, Under-voltage load supply
|
Module parameter |
Deactivate actuator supply, Data format analogue outputs, Diagnosis short circuit actuator supply, Diagnosis parametering error, Diagnosis under-voltage load supply, Behaviour after short circuit/overload actuator supply, Behaviour after short circuit/overload analogue output
|
Channel parameter |
Forces channel x, Approval diagnosis wire break/idle, Approval diagnosis parametering error, Approval diagnosis overload/short circuit, Signal range per channel
|
Fuse (short circuit) |
Internal electronic fuse Per module
|
Intrinsic power input operating voltage load |
Type 15 mA
|
Max. cumulative current outputs per module [A] |
2
|
Nominal operating voltage DC outputs [V] |
24
|
Potential separation channel - internal bus |
yes
|
Potential separation channel - channel |
no
|
Permitted voltage oscillations outputs |
± 25 %
|
Voltage supply, connection type |
2x multi tube holder
|
Voltage supply, connection technology |
Spring tension clamp
|
Voltage supply, number of poles/wires |
4
|
Voltage supply, conductor cross-section [mm²] |
0.2 to 1.5
|
Voltage supply, information on conductor cross-section |
0.2 - 2.5 mm² for flexible conductor without wire end sleeve
|
Permission |
RCM mark
|
CE certificate (see declaration of conformity) |
to EU EMC directive
|
Oscillation strength |
Transport use test with severity level 1 to FN 942017-4 and EN 60068-2-6
|
Shock resistance |
Shock test with degree of severity 1 to FN 942017-5 and EN 60068-2-27
|
Corrosion resistant class KBK |
0 - No corrosion stressing
|
Bearing temperature [°C] |
-20 to 70
|
Relative humidity |
95 %, Not condensing
|
Protect against direct and indirect contact |
Funktionskleinspannung mit sicherer Trennung (PELV)
|
Protection category |
IP20
|
ambient temperature [°C] |
-5 to 50
|
Information about ambient temperature |
-5 - 60 °C with vertical installation
|
Max. address volume outputs [Byte] |
8
|
Electrical connection: outlet, function |
Analogue output
|
Electrical connection: outlet, connection type |
4x multi tube holder
|
Electrical connection: outlet, connection technology |
Spring tension clamp
|
Electrical connection: outlet, number of pins / wires |
4
|
Electrical connection: outlet, conductor cross-section [mm²] |
0.2 to 1.5
|
Electrical connection: outlet, information on conductor cross-section |
0.2 - 2.5 mm² for flexible conductor without wire end sleeve
|
Fastening type |
With Slot rail
|
Material information |
LABS containing materials included, RoHs compliant
|
Housing material |
PA
|
Intrinsic power input operating voltage electronics/sensors |
Type 60 mA
|
Nominal operating voltage DC electronics / sensor [V] |
24
|
Permitted voltage oscillations electronics/sensors |
± 25 %
|
Measured parameter |
Voltage, Current
|
Repeatability |
±0.05 % at 25 °C
|
Use error limits related to ambient temperature range |
±0,3 %
|
Base error limit at 25 °C |
±0,1 %
|
Power blackout bridging [ms] |
10
|
Signal range |
-10 - 10 V, -20 - 20 mA, -5 - 5 V, 0 - 10 V, 0 - 20 mA, 4 - 20 mA
|
Data format |
15 bit + sign, linear scale
|
Max. line length |
30 m, Shielded
|
Electrical connection: outlet 2, function |
Functional ground
|
Electrical connection: outlet 2, connection type |
Multi tube holder
|
Electrical connection: outlet 2, connection technology |
Spring tension clamp
|
Electrical connection: outlet 2, number of pins / wires |
4
|
Electrical connection: outlet 2, wiring diagram |
00995842
|
Electrical connection: outlet 2, conductor cross-section [mm²] |
0.2 to 1.5
|
Electrical connection: outlet 2, information on conductor cross-section |
0.2 - 2.5 mm² for flexible conductor without wire end sleeve
|