Dimensions W x L x H |
18.9 mm x 76.6 mm x 124.3 mm
|
Pitch dimension [mm] |
18,9
|
Diagnosis via LED |
Error per module, Status per channel
|
Diagnosis via bus |
Under-voltage, general error, Device missing/failed, Wire break, Module error, Short circuit, Parameter error, under running/over running
|
Module parameter |
Diagnosis short circuit actuator supply, Deactivate sensor supply, Behaviour after short circuit/overload
|
Channel parameter |
Deactivate actuator supply, Device error code, Force channel x, Channel mode, channel status, cycle time
|
Fuse (short circuit) |
internal electronic fuse, load per channel, internal electronic fuse, sensor per module
|
Intrinsic power input operating voltage load |
Type 15 mA
|
Nominal operating voltage DC outputs [V] |
24
|
Potential separation channel - internal bus |
no
|
Potential separation channel - channel |
no
|
Permitted voltage oscillations outputs |
± 25 %
|
Voltage supply, connection type |
Multi tube holder
|
Voltage supply, connection technology |
Spring tension clamp
|
Voltage supply, number of poles/wires |
4
|
Voltage supply, conductor cross-section [mm²] |
0.2 to 1.5
|
Voltage supply, information on conductor cross-section |
0.2 - 2.5 mm² for flexible conductor without wire end sleeve
|
Permission |
RCM mark
|
CE certificate (see declaration of conformity) |
to EU EMC directive
|
Oscillation strength |
Transport use test with severity level 1 to FN 942017-4 and EN 60068-2-6
|
Shock resistance |
Shock test with degree of severity 1 to FN 942017-5 and EN 60068-2-27
|
Corrosion resistant class KBK |
0 - No corrosion stressing
|
Bearing temperature [°C] |
-20 to 70
|
Relative humidity |
95 %, Not condensing
|
Protect against direct and indirect contact |
Funktionskleinspannung mit sicherer Trennung (PELV)
|
Protection category |
IP20
|
ambient temperature [°C] |
-5 to 50
|
Information about ambient temperature |
-5 - 50 °C with horizontal installation
|
Fastening type |
With Slot rail
|
Material information |
LABS containing materials included, RoHs compliant
|
Housing material |
PA
|
Intrinsic power input operating voltage electronics/sensors |
Type 50 mA
|
Nominal operating voltage DC electronics / sensor [V] |
24
|
Permitted voltage oscillations electronics/sensors |
± 25 %
|
Report |
IO-Link
|
IO-Link, report |
Master V 1.1
|
IO-Link, communication mode |
configurable using software, SIO, COM1 (4.8 kBaud), COM2 (38.4 kBaud), COM3 (230.4 kBaud)
|
IO-Link, port type |
B
|
IO-Link, number of ports |
4
|
IO-Link, process data width OUT |
Parameterisable 8 - 32 Bytes
|
IO-Link, process data width IN |
Parameterisable 8 - 32 Bytes
|
IO-Link, minimum cycle time |
Depends on minimum supported cycle time of the connected IO link devices
|
IO-Link, communication |
C/Q LED green
|
Electrical connection IO link, connection type |
4x multi tube holder
|
Electrical connection IO link, connection technology |
Spring tension clamp
|
Electrical connection IO link, number of pins / wires |
6
|
Electrical connection IO link, conductor cross-section [mm²] |
0.2 to 1.5
|
Electrical connection IO link, information on conductor cross-section |
0.2 - 2.5 mm² for flexible conductor without wire end sleeve
|