Permission |
RCM mark, c UL us - Listed (OL)
|
CE certificate (see declaration of conformity) |
acc. to EU-EMV Directive, acc. to EU-RoHS Directive
|
KC-mark |
KC-EMV
|
Certified awarding point |
UL E322346
|
Material information |
RoHs compliant
|
Measured parameter |
Voltage
|
Signal range |
0 - 10 V
|
ambient temperature [°C] |
0 to 50
|
Sampling interval type [ms] |
1
|
Accuracy FS [%FS] |
0,5
|
Repeatability in ± %FS [%FS] |
0,2
|
Control output |
2 x PNP or 2 x NPN switchable
|
Switch function |
Freely programmable
|
Switching element function |
Opener/closer switchable
|
Max. output current [mA] |
100
|
Short circuit resistance |
yes
|
Report |
IO-Link
|
IO-Link, report |
Device V 1.1
|
IO-Link, profile |
Smart sensor profile
|
IO-Link, function classes |
Teach channel, Diagnosis, Identification, Binary data channel (BDC), Process data variables (PDV)
|
IO-Link, communication mode |
COM2 (38.4 kBaud)
|
IO-Link, SIO mode support |
yes
|
IO-Link, port type |
A
|
IO-Link, process data width OUT |
0 Bytes
|
IO-Link, process data width IN |
5 Bytes
|
IO-Link, process data contents IN |
14 bit PDV (measurement InA), 14 bit PDV (measurement value InB), 2 bit BDC (measurement monitoring)
|
IO-Link, minimum cycle time |
5 ms
|
IO-Link, data memory needed [Byte] |
500
|
Operating voltage range DC [V] |
15 to 30
|
Reverse polarity protection |
for all electrical connections
|
Electrical connection 1, connection type |
Plug
|
Electrical connection 1, connection technology |
Wiring diagram L1J
|
Electrical connection 1, number of pins / wires |
4
|
Electrical connection 2, connection type |
2x socket
|
Electrical connection 2, connection technology |
Wiring diagram EC
|
Electrical connection 2, number of pins / wires |
4
|
Fastening type |
Front panel integration, With Wall / flat holder
|
Housing material |
PA reinforced
|
Display type |
Illuminating LCD Multiple
|
Setting options |
IO-Link, Teach-In, über Display und Tasten
|
Tamper-proof fuse |
IO-Link, PIN code
|
Protection category |
IP40
|
Corrosion resistant class KBK |
2 - moderate corrosion stress
|